Brand Name : alphaclean
Model Number : 24*24*12" 595 * 595 * 292
Place of Origin : china
MOQ : 1 pc
Price : negotiation
Payment Terms : L/C, T/T
Supply Ability : 200pcs per week
Delivery Time : 5-8 days
Packaging Details : Polywood packing
Material : fiberglass , PP
Efficiency : 99.99%
Usage : Final or return filtration for clean rooms
Construction : BOX Filter
Porosity : 0.3um,0.12 um,0.5un
Frame : ABS
Type : Hepa Filter/ ULPA filter
Application : Industrial cleanroom,Free dust room,Hospital
0.3um Porosity ABS Frame 3V H14 Compact HEPA Filter Replacement
3V Compact H14 HEPA Filter With ABS Frame 592 x 490 x 292
V Cell filters, also be called as v bank filters, rigid pocket filters,are the most important part in clean room ventilation systems when filtration level 100 or 10.
V cell filters are pre-filters before HEPA filters, the role and function are the same as pocket filters, but v bank filters offer more stable performance.
The ‘V’ design provides significantly more surface area than pocket filters, reducing the overall pressure drop in the system and extending HEPA filters life.
To enlarge the service life of HEPA filters, V bank filters need to remove most of the 0.5um particles with efficiency from 75-99%.
Normally, the v bank filters are made of ABS plastic frame, mini pleated glass fiber or pp pack, hot melt glue as the separator, they are manufactured in a doubleheader frame and are relatively lightweight when compared to the overall capacity of the products.
Compact V Cell H14 HEPA Filter With Abs Frame For Air Filtration System
Application: Air intake for gas turbines, compressors and large engines.
Type: High efficiency, incinerable compact filter.
Frame: Polypropylene and ABS.
Gasket: Expanded polyurethane placed on the downstream side (code 01).
Media: Glass fibre paper.
Separator: Hot-melt beads.
Sealant: Polyurethane.
Grid: Glass fibre reinforcement grid placed downstream.
EN 779:2002 efficiency: F7. F8 F9.
EN 1822 efficiency: H10.
Recommended final pressure drop: 600 Pa.
Temperature: 80°C maximum in continuous service.
N.B: Burst pressure: > 7500 Pa.
Optional: Alternative frame materials and size available on request.
Standard specification
Dimension (mm) (W*H*D) | Pack NO | Rate Air Flow (m3/h) | Media Area (m2) | Dust Holding (g) | Efficiency | Rate primary Resistance (Pa) | Finally Resistance (Pa) |
592X287X292 | 4 | 2100 | 11.02 | 660 | F7 65%@0.5um |
<80Pa |
300-350pa |
592X490X292 | 4 | 3550 | 18.6 | 1200 | |||
592X592X292 | 4 | 4500 | 22.1 | 1350 | |||
610X610X292 | 5 | 5400 | 29 | 1750 | |||
592X287X292 | 4 | 2100 | 11.02 | 660 | F8 85%@0.5um |
<100pa |
350-400pa |
592X490X292 | 4 | 3550 | 18.6 | 1200 | |||
592X592X292 | 4 | 4500 | 22.1 | 1350 | |||
610X610X292 | 4 | 5400 | 29 | 1750 | |||
592X287X292 | 4 | 2100 | 11.02 | 660 | F9 90%@0.5um |
<120pa |
400-450pa |
592X490X292 | 4 | 3550 | 18.6 | 1200 | |||
592X592X292 | 4 | 4500 | 22.1 | 1350 | |||
610X610X292 | 5 | 5400 | 29 | 1750 |
![]() |